| Kernel driver g762 | |
| ================== | |
| The GMT G762 Fan Speed PWM Controller is connected directly to a fan | |
| and performs closed-loop or open-loop control of the fan speed. Two | |
| modes - PWM or DC - are supported by the device. | |
| For additional information, a detailed datasheet is available at | |
| http://natisbad.org/NAS/ref/GMT_EDS-762_763-080710-0.2.pdf. sysfs | |
| bindings are described in Documentation/hwmon/sysfs-interface. | |
| The following entries are available to the user in a subdirectory of | |
| /sys/bus/i2c/drivers/g762/ to control the operation of the device. | |
| This can be done manually using the following entries but is usually | |
| done via a userland daemon like fancontrol. | |
| Note that those entries do not provide ways to setup the specific | |
| hardware characteristics of the system (reference clock, pulses per | |
| fan revolution, ...); Those can be modified via devicetree bindings | |
| documented in Documentation/devicetree/bindings/hwmon/g762.txt or | |
| using a specific platform_data structure in board initialization | |
| file (see include/linux/platform_data/g762.h). | |
| fan1_target: set desired fan speed. This only makes sense in closed-loop | |
| fan speed control (i.e. when pwm1_enable is set to 2). | |
| fan1_input: provide current fan rotation value in RPM as reported by | |
| the fan to the device. | |
| fan1_div: fan clock divisor. Supported value are 1, 2, 4 and 8. | |
| fan1_pulses: number of pulses per fan revolution. Supported values | |
| are 2 and 4. | |
| fan1_fault: reports fan failure, i.e. no transition on fan gear pin for | |
| about 0.7s (if the fan is not voluntarily set off). | |
| fan1_alarm: in closed-loop control mode, if fan RPM value is 25% out | |
| of the programmed value for over 6 seconds 'fan1_alarm' is | |
| set to 1. | |
| pwm1_enable: set current fan speed control mode i.e. 1 for manual fan | |
| speed control (open-loop) via pwm1 described below, 2 for | |
| automatic fan speed control (closed-loop) via fan1_target | |
| above. | |
| pwm1_mode: set or get fan driving mode: 1 for PWM mode, 0 for DC mode. | |
| pwm1: get or set PWM fan control value in open-loop mode. This is an | |
| integer value between 0 and 255. 0 stops the fan, 255 makes | |
| it run at full speed. | |
| Both in PWM mode ('pwm1_mode' set to 1) and DC mode ('pwm1_mode' set to 0), | |
| when current fan speed control mode is open-loop ('pwm1_enable' set to 1), | |
| the fan speed is programmed by setting a value between 0 and 255 via 'pwm1' | |
| entry (0 stops the fan, 255 makes it run at full speed). In closed-loop mode | |
| ('pwm1_enable' set to 2), the expected rotation speed in RPM can be passed to | |
| the chip via 'fan1_target'. In closed-loop mode, the target speed is compared | |
| with current speed (available via 'fan1_input') by the device and a feedback | |
| is performed to match that target value. The fan speed value is computed | |
| based on the parameters associated with the physical characteristics of the | |
| system: a reference clock source frequency, a number of pulses per fan | |
| revolution, etc. | |
| Note that the driver will update its values at most once per second. |